Powerware E.T.N 1500 VA - 60kVa User Manual

Page 45

Advertising
background image



www.powerware.com

1.800.356.5794

SINGLE-PHASE SERIES 9
Powerware 9155 (continued)

POWERWARE 9 SPARE PARTS

PW9155 Spares Kit

106711155

$7,805

POWERWARE 9 UPGRADES

Powerware 9155 - 2 Unit Parallel Upgrade Kit

4

103004626

$998

Powerware 9155 - 3 Unit Parallel Upgrade Kit

4

103004627

$1,497

1. Up to three PW9155 UPSs can be paralleled with the Parallel Cabinet. 2. Each Powerware 9155 UPS must have a Powerware Hot Sync Bridge CAN Card installed in the second X-Slot Communication
Bay. 3. If extended runtime is required for the application, then each UPS must have its own EBM and the same number of EBM(s). 4. Kit includes CAN Bridge Card and instructions.


POWERWARE 9 BATTERY BACKUP TIMES (in minutes) @ 0.9 POWER FACTOR

Load

UPS + Internal

UPS + Internal

(VA/Watt)

32 Battery +(1) EBM 64 +(2) EBM 64 +(3) EBM 64 +(4) EBM 64

64 Battery

+(1) EBM 96

+(2) EBM 96 +(3) EBM 96

15000/13500

4.6

23.0

43.0

65.1

88.6

13.3

43.0

76.7

113.0

14500/13050

4.9

24.1

45.2

68.3

93.0

14.1

45.2

80.5

119.0

14000/12600

5.2

25.2

47.3

71.5

97.4

14.9

47.3

84.2

125.0

13500/12150

5.5

26.4

49.4

74.7

102.0

15.8

49.4

88.1

130.0

13000/11700

5.8

27.6

51.6

78.1

106.0

16.7

51.6

92.0

136.0

12500/11250

6.1

28.8

54.0

81.6

111.0

17.6

54.0

96.2

142.0

12000/10800

6.5

30.2

56.5

85.5

116.0

18.6

56.5

101.0

149.0

11500/10350

6.9

31.6

59.3

89.7

122.0

19.2

59.3

106.0

156.0

11000/9900

7.3

33.3

62.4

94.4

129.0

20.2

62.4

111.0

164.0

10500/9450

7.8

35.1

65.9

99.6

136.0

21.4

65.9

117.0

174.0

10000/9000

8.4

37.2

69.8

106.0

144.0

22.6

69.8

124.0

184.0

9500/8550

9.1

39.6

74.2

112.0

153.0

24.1

74.2

132.0

196.0

9000/8100

9.9

42.3

79.4

120.0

163.0

25.7

79.4

141.0

209.0

8500/7650

10.8

45.5

85.2

129.0

175.0

27.6

85.2

152.0

225.0

8000/7200

11.9

49.1

91.9

139.0

189.0

29.8

91.9

164.0

242.0

7500/6750

13.1

53.2

99.7

151.0

205.0

32.3

99.7

178.0

263.0

7000/6300

14.6

58.0

109.0

164.0

224.0

35.2

109.0

194.0

286.0

6500/5850

16.3

63.5

119.0

180.0

245.0

38.6

119.0

212.0

314.0

6000/5400

18.4

70.0

131.0

198.0

270.0

42.5

131.0

234.0

346.0

5500/4950

20.1

77.6

145.0

220.0

300.0

47.2

145.0

259.0

383.0

5000/4500

22.4

86.6

162.0

245.0

334.0

52.6

162.0

289.0

428.0

4500/4050

25.2

97.4

182.0

276.0

376.0

59.2

182.0

325.0

-

4000/3600

28.6

110.0

207.0

313.0

426.0

67.1

207.0

369.0

-

3500/3150

32.8

127.0

238.0

359.0

-

77.0

238.0

423.0

-

3000/2700

38.3

148.0

277.0

418.0

-

89.7

277.0

-

-

2500/2250

45.6

176.0

329.0

-

-

107.0

329.0

-

-

Note: Backup times are approximate and may vary with equipment, configuration, battery age, temperature, etc.

Advertising