R3.0

Page 10 of 62

2.3 Peak Voltage Charge

2.3.1. Nominal Battery Voltage

2.3.1.1. Enter the nominal battery voltage using the cell selector (see chart on

page

xxx

).

2.3.1.2. Select transfer from Main to Topping on Peak or stop on Peak.

2.3.1.3. Program the Main and Topping Charge currents as required.

2.3.1.4. Program the Main and Total Time selectors to allow the battery to

reach the required charge level (consult battery manufacturers
specifications). Verify that the Timer Speed is consistent with the
required elapsed time.

2.3.1.5. Start the Charger-Analyzer in the Dual Rate mode. The charger will

transfer from Main to Topping charge when the battery reaches the
peak voltage or Start in the Dual or Single Rate mode and the Charger-
Analyzer will stop on peak (at any part of the cycle).

2.3.1.6. The charge will terminate automatically (CYCLE END) when the

TOTAL TIME selected is reached.

2.3.1.7. The charge will terminate as a FAULT if the MONITOR CIRCUIT

detects that:

• Battery temperature exceeds 45

o

C/113

o

F (BATTERY

OVERTEMP FAULT).

• The actual charge current deviates from the programmed value by

more than one AMP (CURRENT FAULT).