INSTALLATION

EATON Powerware

®

9125 Two-in-One UPS (5000/6000 VA) User’s Guide

S 164201513 Rev B

www.powerware.com

24

Hardwired UPS Installation

W A R N I N G

Only qualified service personnel (such as a licensed electrician) shall perform the electrical
installation. Risk of electrical shock.

C A U T I O N

S

For UPS models with hardwired outputs, overcurrent protection for the output AC
circuit(s) is to be provided by others.

S

For UPS models with hardwired outputs, suitably rated disconnect switches for the
output AC circuit(s) are to be provided by others.

NOTE Do not make unauthorized changes to the UPS; otherwise, damage may occur to
your equipment and void your warranty.

The Powerware 9125 hardwired models require a dedicated branch
circuit that meets the following requirements:

S

40A minimum circuit with short circuit and overcurrent protection

S

200–240 Vac

S

Single-phase

S

50/60 Hz

S

The breaker must be wall-mounted and be readily accessible to the
operator

S

Flexible metal conduit (recommended for ease of service and
maintenance)