CONFIGURATION

EATON Powerware

®

9125 Two-in-One UPS (5000/6000 VA) User’s Guide

S 164201513 Rev B

www.powerware.com

36

1

Press and hold the On and Test/Alarm
Reset buttons simultaneously for three
seconds to toggle between Configuration
and Operation modes.

&

4

Press the Test/Alarm Reset
button ONCE to select the
option.

3

Press the On button to
scroll to the next option.

2

On Button

Test/Alarm
Reset Button

Bar Graph Indicators

Figure 17. Using Configuration Mode

Table 2. Configuration Mode LEDs and Options

Bar Graph Indicators

Option

LED Status

Explanation

240V Nominal Output
Voltage

On

Nominal output voltage is 240V.
All other nominal output voltages are disabled.

Flashing

240V is disabled; one of the other output voltage
options is selected.

230V Nominal Output
Voltage

On

Nominal output voltage is 230V.
All other nominal output voltages are disabled.

Flashing

230V is disabled; one of the other output voltage
options is selected.

220V Nominal Output
Voltage

On

Nominal output voltage is 220V.
All other nominal output voltages are disabled.

Flashing

220V is disabled; one of the other output voltage
options is selected.

208V Nominal Output
Voltage

On

Nominal output voltage is 208V.
All other nominal output voltages are disabled.

Flashing

208V is disabled; one of the other output voltage
options is selected.

Site Wiring Fault
Alarm

On

Alarm sounds when the polarity of the outlet is
reversed or the ground connection is missing; have a
qualified electrician repair the outlet wiring.

Flashing
(default)

Alarm DOES NOT sound when the polarity of the outlet
is reversed or the ground connection is missing.