Powerware 9125 Two-in-One UPS 6000 VA User Manual

Page 32

Advertising
background image

INSTALLATION

EATON Powerware

®

9125 Two-in-One UPS (5000/6000 VA) User’s Guide

S 164201513 Rev B

www.powerware.com

26

6.

Connect the input and ground wires to the UPS terminal block
according to Figure 13 and Table 1.

7.

Connect the output and ground wires to the UPS terminal block
according to Figure 13 and Table 1.

L1 Out

Output
Ground

L1 In

L2/Neutral In

L2/Neutral Out

Input

Ground

No Connection

Figure 13. UPS Terminal Block

Table 1. UPS Wiring Specifications

UPS Terminal

Block

Terminal

Position

UPS Wire Function

Terminal Wire

Size Rating*

Tightening

Torque

Input

1

Input Ground

2

L1 In

2.5–16 mm

2

(14–6 AWG)

1.8 Nm (16 lb in)

3

L2/Neutral In

(14–6 AWG)

(

)

No Connection

4

No Connection

Output

5

L1 Out

6

L2/Neutral Out

2.5–16 mm

2

(14–6 AWG)

1.8 Nm (16 lb in)

7

Output Ground

(14–6 AWG)

(

)

* Use 2.0 mm

2

(14 AWG) 75_C copper wire minimum.

Advertising