How to replace internal batteries – Powerware 9125 Two-in-One UPS 6000 VA User Manual

Page 50

Advertising
background image

UPS MAINTENANCE

EATON Powerware

®

9125 Two-in-One UPS (5000/6000 VA) User’s Guide

S 164201513 Rev B

www.powerware.com

44

How to Replace Internal Batteries

C A U T I O N

S

The UPS battery trays are heavy (28.1 kg/62 lb). A minimum of two people are required
to lift the battery trays into the UPS chassis.

S

Pull the battery trays out onto a flat, stable surface. The battery trays are unsupported
when you pull them out of the UPS.

To replace the internal batteries:

1.

Switch the battery breaker on the UPS rear panel to the OFF (O)
position.

2.

Remove the lower UPS front cover (see Figure 22).

Figure 22. Removing the Lower UPS Front Cover

3.

Unscrew and set aside the battery retaining bracket (see Figure 23).

Battery Retaining
Bracket

Figure 23. Removing the Battery Retaining Bracket

4.

Pull the battery trays out onto a flat, stable surface (see Figure 24).
See “Recycling the Used Battery or UPS” on page 46 for proper
disposal.

Figure 24. Removing the Battery Trays