Chapter 7 ups maintenance, Ups and battery care, When to replace batteries – Powerware 9125 Two-in-One UPS 6000 VA User Manual

Page 47

Advertising
background image

EATON Powerware

®

9125 Two-in-One UPS (5000/6000 VA) User’s Guide

S 164201513 Rev B

www.powerware.com

41

Chapter 7

UPS Maintenance

This section explains how to:

S

Care for the UPS and batteries

S

Replace the batteries

S

Test new batteries

S

Recycle used batteries or UPS

UPS and Battery Care

For the best preventive maintenance, keep the area around the UPS
clean and dust-free. If the atmosphere is very dusty, clean the outside of
the system with a vacuum cleaner.

For full battery life, keep the UPS at an ambient temperature of
25°C (77°F).

NOTE If the UPS requires any type of transportation, verify that the battery circuit breaker
on the UPS rear panel is in the OFF (O) position (see Figure 9 on page 20).

NOTE The batteries in the UPS are rated for a 3–5 year service life. The length of service
life varies, depending on the frequency of usage and ambient temperature. Batteries used
beyond expected service life will often have severely reduced runtimes. Replace batteries at
least every 5 years to keep units running at peak efficiency.

Storing the UPS and Batteries

If you store the UPS for a long period, recharge the battery every
10 months by connecting the UPS to utility power. The batteries charge
to 80% capacity in less than 2 hours. However, it is recommended that
the batteries charge for 24 hours after long-term storage.

Check the battery recharge date on the shipping carton label. If the date
has expired and the batteries were never recharged, do not use the
UPS. Contact your service representative.

When to Replace Batteries

When the

indicator flashes, the batteries may need replacing.

Contact your service representative to order new batteries.

Advertising
This manual is related to the following products: