INSTALLATION

EATON Powerware

®

9125 Two-in-One UPS (5000/6000 VA) User’s Guide

S 164201513 Rev B

www.powerware.com

27

8.

Replace the wiring access cover and the conduit landing plate.

9.

Remove the breaker tie from all battery circuit breakers.

10. Switch all battery circuit breakers to the ON (

|

) position.

11. If an emergency power-off (disconnect) switch is required by local

codes, see “Remote Emergency Power-off Installation” on page 22
to install the REPO switch before powering on the UPS.

12. Switch the main utility breaker on.

The

μ

indicator flashes, indicating the UPS is in Standby mode

with the equipment offline.

13. Press the On

button (see Figure 14 on page 31).

The

μ

indicator illuminates solid and the bar graph indicators

display the percentage of load being applied to the UPS. The UPS is
now in Normal mode and supplying power to your equipment.

The UPS automatically sets the output voltage based on the input
voltage. To change the output voltage, see “Configuration” on
page 35.

NOTE The batteries charge to 80% capacity in less than 2 hours. However, it is
recommended that the batteries charge for 24 hours after installation or long-term storage.

NOTE If you installed power management software and optional EBMs, ensure maximum
battery runtime by using the Virtual Front Panel UPS utility on the Software Suite CD.