Selecting the correct size erv, Commercial and institutional requirements – Lifebreath 200ERVD User Manual

Page 5

Advertising
background image

5

MAKE UP HEAT REQUIREMENT at 1200 CFM (566L/s)

Nominal

Nominal

Nominal

Outdoor Temp.

kW Req. for

kW Req. for

kW Req. for

20°C (68°F)

25°C (77°F)

30°C (86°F)

Air Delivery

Air Delivery

Air Delivery

0 32

7

10

14

-10 14

10

14

17

-20 -4

12

15

19

-30 -22

15

19

22

-40 -40

17

21

24

Selecting the Correct Size ERV

Commercial and Institutional Requirements

For outdoor air requirements, ASHRAE has produced the Ventilation Standard 62-1989 that
is used to determine acceptable ventilation rates. This standard is referenced directly or
used as “Good Engineering Practice” in most Code documents or design criteria.

Small restaurants, Donut Shops and Fast food stores

Seats

40

Employees

5

Total

45

ASHRAE requirement

20 cfm (10L/s) per person

Ventilation required

45 x 20 = 900 cfm (450 L/s)

Bank

Customers

25

Staff

9

Total

34

ASHRAE requirement

20 cfm (10L/s) per person

Ventilation required

34 x 20 = 680 cfm (320 L/s)

Bar or Tavern

Seats

50

Employees

7

Total

57

ASHRAE requirement

30 cfm (15L/s) per person

Ventilation required

57 x 30 = 1710 cfm (855 L/s)

Bingo Hall

Customers

180

Staff

20

Total

200

ASHRAE requirement

30 cfm (15L/s) per person

Ventilation required

200 x 30 = 6000 cfm (3000 L/s)

Classroom and School Portables

Seats

29

Teacher

1

Total

30

ASHRAE requirement

15 cfm (7.5L/s) per person

Ventilation required

30 x 15 = 450 cfm (255 L/s)

Print Shop, Duplicating

Square footage of shop

2000 square ft (m

2

)

ASHRAE requirement

0.5 cfm/ft2 (2.5L/s - m

2

)

per person

Ventilation required

2000 x 0.5 = 1000 cfm (500 L/s)

Beauty Salon

Customers

12

Employees

6

Total

18

ASHRAE requirement

25 cfm (12.5L/s) per person

Ventilation required

18 x 25 = 450 cfm (255 L/s)

Swimming Pools

1 cfm per sq. ft. of the water surface area

or

0.5 cfm per sq. ft. of the water surface plus deck area

Hot Tubs

7 - 10 cfm per sq. ft. of the water surface area