SPECIFICATIONS

LATENT RECOVERY (MOISTURE) TRANSFER CORES
Modular (2 section) enthalpic (moisture) transfer cores arranged for
efficient cross-flow ventilation.

MOTORS
Two PSC, 3 speed single shafted, 120 VAC, 2.75 Amps each (5.5 total
on high speed). HP - 1/10, 1625 RPM. Watts - total on high speed - 648.

FILTERS
Washable air filters in exhaust and supply air streams.

BLOWERS
Centrifugal type rated at 700 CFM (329 L/s) free air delivery. Each air
stream has one single shafted motor driving a centrifugal blower.

CONNECTION DUCT SIZES
Four - 14" x 8" (356 mm x 200 mm)

MOUNTING
Unit to be set on support brackets hung by threaded rod type
apparatus (brackets and rods not provided).

CASE
20 gauge prepainted galvanized steel (G60) for superior corrosion
resistance. Insulated with foil faced insulation where required to pre-
vent exterior condensation.

CONTROLS
Illuminated power switch, 3 speed blower control, low voltage (24
VAC) terminals for connection of remote controls.

WEIGHT

142 lbs (64.4 kg)

SHIPPING WEIGHT 167 lbs. (75.8 kg)

All units conform to CSA and UL standards.

WARRANTY
Units carry a 5 year warranty on the energy recovery cores and
2 year replacement parts warranty.

It is recommended for regions where the temperature
does not fall below 25°F (-4°C).

DATE:

_________________________________________

PROJECT:

______________________________________

MECHANICAL CONTRACTOR:

__________________________

TI-131

9807

511 McCormick Blvd.
London, ON N5W 4C8
Phone: (519) 457-1904
Fax: (519) 457-1676
E mail: nutech@lifebreath .com

AIRFLOWS (Each Air Stream)

MODEL 700FD, 700DD

423 (900)

378 (800)

329 (700)

282 (600)

235 (500)

190 (400)

143 (300)

94 (200)

42 (100)

AIRFLOW L/s (CFM)

25 (.1) 50 (.2) 75 (.3) 100 (.4) 125 (.5) 150 (.6) 175 (.7)

EXTERNAL STATIC PRESSURE IN PASCALS (IN. W.C.)

TOTAL CURRENT DRAW (AMPS) @ 120 VAC

5.5 HIGH

4.7 LOW

70%

60%

50%

143

(300)

190

(400)

235

(500)

282

(600)

329

(700˚)

TEMPERATURE EFFECTIVENESS

AIRFLOW IN L/s (CFM)

NOTE: Exhaust Relative Humidity (RH) at 40%

EFFECTIVENESS

HIGH SPEED

MED SPEED

LOW SPEED

5.0 MED

P E R F O R M A N C E

29 5/8" (753 mm)

8"

(200 mm)

FRONT VIEW

625 mm

(24 5/8 ")

28 3/4"

(730 mm)

14"

(356 mm)

8 1/4"

(210 mm)

INLET SIDE

DIMENSIONS 700

inches (mm)

8"

(200 mm)

28 3/4"

(730 mm)

14"

(356 mm)

6 1/4"

(159 mm)

MOUNTING POINTS

CONTROLS

DISCHARGE SIDE

EXHAUST AIR

TO OUTSIDE

EXHAUST AIR

FROM BUILDING

SUPPLY AIR

TO BUILDING

SUPPLY AIR

FROM OUTSIDE

NOTE:
Service clearance
is 30 in. (760 mm)

HEAT RECOVERY VENTILATORS (HRVs)

®

6 1/2"

(165 mm)

6 1/2"

(165 mm)

Advertising