S P E C I F I C A T I O N S

LATENT RECOVERY (MOISTURE) TRANSFER CORES
Modular (4 section) 2- Enthalpic, 2 Aluminum arranged for high
efficiency crossflow ventilation.

MOTORS - Two PSC, 5 speed double shafted, 120 VAC, 3.15 Amps each (6.3
total on high speed). HP - 1/10, 1625 RPM. Watts - total on High Speed - 610.

FILTERS - Washable air filters in exhaust and supply air streams.

BLOWERS - Centrifugal type rated at 530 cfm (250 L/s) free air delivery.
Each air stream has two centrifugal blowers driven by two PSC motors.

CONNECTION DUCT SIZES Four - 14" x 8" (356 mm x 200 mm).

MOUNTING - Unit to be set on support brackets hung by threaded rod
type apparatus (brackets and rods not included).

DEFROST

- Damper defrost system.

CASE - 20 gauge prepainted galvanized steel (G60) for superior corrosion
resistance. Insulated with foil faced insulation duct liner where required to
prevent exterior condensation. Drain connection, One - 1/2" (12 mm) O.D.

CONTROLS - ControlAir 15

WEIGHT

178 lbs. (81 kg)

SHIPPING WEIGHT

203 lbs. (92 kg)

8

Model 500ERV

®

C L E A N • F R E S H • A I R

49"

(1245 mm)

8"

(200 mm)

FRONT VIEW

18 3/4"

(475 mm)

28 1/4 "

(717 mm)

14"

(356 mm)

5 7/8"

(150 mm)

1 1/4"

(32 mm)

INTERIOR DUCT

CONNECTION SIDE

18 3/4"

(475 mm)

8"

(200 mm)

28 1/4"

(717 mm)

14"

(356 mm)

5 7/8"

(150 mm)

1 3/8"

(35 mm)

EXTERIOR DUCT

CONNECTION SIDE

MOUNTING POINTS

DRAIN CONNECTION

DIMENSIONS 500 ERV

inches (mm)

EXHAUST AIR

TO OUTSIDE

EXHAUST AIR

FROM BUILDING

SUPPLY AIR

TO BUILDING

SUPPLY AIR

FROM OUTSIDE

NOTE:
Service clearance
is 30 in. (760 mm)

DEFROST

OPTIONS

99-104

Digital Electronic Timer - 20/40/60 min. (3 wire)

99-105

Programmable Ventilation Control includes
Programmable Time Clock, Dehumidistat and
Air Sentry™

99-109

Air Sentry™ Air Quality Monitor

All units conform to CSA and UL standards.

WARRANTY

Units carry a 5 year warranty on the energy recovery cores and
15 years on aluminum cores. Two (2) year replacement parts
warranty.

It is recommended for regions where the temperature does

not drop below 25°F (-4°C).

DATE:

________________

UNIT SELECTED:

_____________

PROJECT:

________________________________________

MECHANICAL CONTRACTOR:

__________________________

AIRFLOWS (Each Air Stream)

282 (600)

235 (500)

190 (400)

143 (300)

94 (200)

42 (100)

AIRFLOW L/s (CFM)

25 (.1) 50 (.2) 75 (.3) 100 (.4) 125 (.5)

EXTERNAL STATIC PRESSURE IN PASCALS (in. W.C.)

TOTAL CURRENT DRAW (AMPS) @ 120 VAC

6.3 HIGH

3.1 LOW

100%

90%

80%

143

(300)

190

(400)

235

(500)

282

(600)

TEMPERATURE EFFECTIVENESS

AIRFLOW IN L/s (CFM)

NOTE: Exhaust Relative Humidity (RH) at 40%

EFFECTIVENESS

SPEED

5

3

4

2
1

LIFEBREATH 500

LIFEBREATH 500

3.8 MED

94

(200)

P E R F O R M A N C E

511 McCormick Boulevard.
London, ON N5W 4C8

Phone: (519) 457-1904
Fax: (519) 457-1676
E mail:[email protected]

TI-130