ENGINEERING DATA

LATENT RECOVERY/MOISTURE TRANSFER CORE
The cross-flow energy recovery core transfers heat and water vapour
between the two airstreams. It is easily removed for cleaning or service.

MOTORS AND BLOWERS

- Each air streams has one centrifugal blower

driven by a common PCS motor. 5 speed fan operation.
High speed - 120 VAC, 1.4 Amps, 164 Watts.

FILTERS

- Washable air filters in exhaust and supply air streams.

MOUNTING THE ERV

- Four 10/24" (10.5 mm) threaded inserts at

corners of case designed to accept four PVC reinforced polyester straps
that are supplied with the unit.

DEFROST

- Damper defrost system.

CASE

- Twenty gauge prepainted galvanized steel (G60) for superior

corrosion resistance. Insulated to prevent exterior condensation.

DRAIN CONNECTIONS

- Two - 1/2” (12mm) O.D.

CONTROLS

- ControlAir 15

WEIGHT

63 lbs. (28.7 kg)

SHIPPING WEIGHT

65 lbs. (29.6 kg )

PERFORMANCE

HVI CERTIFIED

Net supply airflow in cfm (L/s) against external static pressure

E.S.P

cfm

L/s

@ 0.1” (25 Pa)

195

(92)

@ 0.2” (50 Pa)

185

(87)

@ 0.3” (75 Pa)

175

(83)

@ 0.4” (100 Pa)

160

(76)

@ 0.5” (125 Pa)

145

(68)

Sensible Effectiveness
@ 110 L/s (55 cfm)

(CSA C439M)

80%

Sensible Efficiency
@ 110L/s (55 cfm) @0

O

C (32°F)

70%

Sensible Efficiency
@ 110 L/s (55 cfm) @ -25

O

C (-13°F)

55%

VAC @ 60HZ

120

WATTS / Low speed

80

Amp rating

1.4

STALE AIR

TO OUTSIDE

STALE AIR

FROM HOUSE

FRESH AIR

TO INSIDE

14

3

/

4

"

(375)

19"

(483)

DIMENSIONS 200 ERVD

inches (mm)

*

All Duct Connections 6"(150mm)

FILTERS

BLOWERS

*NOTE: Front clearance
of 25 inches (635 mm)
is recommended
for servicing unit.

MOTOR

31"

(787)

FRESH AIR

FROM OUTSIDE

DAMPER

DEFROST

PORT

CONDENSATE DRAINS

OPTIONS

99-104 Digital Electronic Timer - 20/40/60 min. (3 wire)

99-105 Deluxe Programmable Control includes

Programmable Time Clock, Dehumidistat

and Air Sentry™

99-109 Air Sentry™ Air Quality Monitor

99-186 Weatherhoods, Two - 6” (150mm)

c/w 1/4” (6mm) mesh screen

WARRANTY

Units carry a 5 year warranty on the energy recovery core and
replacement parts.

All units are CSA and UL standards.

It is not recommended for regions where the temperature
does not drop below 25°F (-4°C)

DATE:

__________________________

PROJECT:

___________________________________

MECHANICAL CONTRACTOR:

__________________________

511 McCormick Blvd.
London, ON N5W 4C8
Phone: (519) 457-1904
Fax: (519) 457-1676
Email: [email protected]

TI-200ERVD

0006

7

Advertising
This manual is related to the following products: