Feedwater regulator, Piping—heating boilers, Temperature & pressure gauge – Raypak RAYTHERM 133-4001 User Manual

Page 18: Maximum and minimum flow rates

Advertising
background image

18

R

D

H

R

D

H

L

E

D

O

M

SIZE

GPM

T

P FT

GPM

T

P FT CONN

GPM

T

P FT

GPM

T

P FT CONN

133*

22

10

14.7

10

22

3.3

1-1/4"

182/181

45

7

9.2

20

15

1.8

1-1/2"

260/261

45

10

9.4

20

22

1.9

1-1/2"

330/331

45

12

9.6

20

28

1.9

1-1/2"

400/401

45

15

9.8

20

33

2.0

1-1/2"

514

90

9

9

40

21

1.8

2"

624

90

12

9.5

40

26

1.9

2"

724

90

13

10

40

30

2.0

2"

824

90

15

10.5

40

34

2.1

2"

926

90

17

11

40

38

2.2

2 1/2"

200

8

9.7

90

17

2.1

3"

962

90

18

11

40

40

2.2

2 1/2"

200

8

9.7

90

18

2.1

3"

1083

90

20

12

45

40

3.1

2 1/2"

200

9

10.3

90

20

2.3

3"

1125

90

21

12

47

40

3.3

2 1/2"

200

9

10.3

90

20

2.3

3"

1178

90

22

12.5

49

40

3.8

2 1/2"

200

10

11

90

21

2.4

3"

1223

90

22

12.5

51

40

4.0

2 1/2"

200

10

11

90

22

2.4

3"

1287

90

24

13.2

53

40

4.5

2 1/2"

200

11

11.7

90

23

2.5

3"

1336

90

24

13.2

55

40

4.9

2 1/2"

200

11

11.7

90

24

2.5

3"

1414

90

26

14

58

40

5.8

2 1/2"

200

12

12.2

90

26

2.7

3"

1468

90

27

14

61

40

6.4

2 1/2"

200

12

12.2

90

27

2.7

3"

1571

90

29

14.5

65

40

7.5

2 1/2"

200

13

13

90

29

2.8

3"

1631

90

30

14.5

68

40

8.3

2 1/2"

200

13

13

90

30

2.8

3"

1758

90

32

15.4

73

40

10.0

2 1/2"

200

14

14.7

90

32

3

3"

1826

90

34

15.4

76

40

10.8

2 1/2"

200

15

14.7

90

33

3

3"

2100

200

17

14.8

90

39

3.2

3"

400

9

18

180

19

4

4"

2500

200

21

15.8

103

40

4.4

3"

400

10

18.8

180

23

4.1

4"

3001

200

25

16.7

124

40

6.7

3"

400

12

19.5

180

27

4.3

4"

3500

200

29

17.5

145

40

9.5

3"

400

14

20.5

180

32

4.5

4"

4001

200

33

18.7

166

40

13.0

3"

400

16

21.5

180

36

4.7

4"

MAXIMUM AND MINIMUM FLOW RATES

2-PASS HEAT EXCANGER

1-PASS HEAT EXCHANGER

N

I

M

X

A

M

N

I

M

X

A

M

GPM Flow rates limited by maximum acceptable velocity through heat exchanger tubes. May be increased by 10% for closed heating
systems.
* 4 Pass Heat Exchanger
BOLD TYPE indicates Low NOx models.

difference between the inlet and outlet water when the

boiler is firing at full rate). For some boilers, the Delta

T is more than 20°F (22°-33°F) at the recommended

flow rates.

Feedwater Regulator

We recommend that a feedwater regulator be installed

and set at 12 PSIG minimum pressure. Install a check

valve or back flow device upstream of the regulator,

with a manual shut-off valve. Leave the valve open.

Piping—Heating Boilers

We recommend that all high points be vented and that

purge valves and a bypass valve be installed. A boiler

installed above radiation level must be provided with a

low water cut-off device. The boiler, when used in con-

junction with a refrigeration system, must be installed

so that the chilled medium is piped in parallel with the

boiler with appropriate valves to prevent the chilled

medium from entering the boiler.

Recommended Purge Manifolds for

Typical Hydronic System Hookups

The boiler piping system of a hot water heating boiler

connected to heating coils located in air handling units

where they may be exposed to refrigerated air circulat-

ing, must be equipped with flow control valves or other

automatic means to prevent gravity circulation of the

boiler water during the cooling cycle.

Temperature & Pressure Gauge

The temperature & pressure gauge is standard equip-

ment on all hydronic heating and hot water supply

boilers. All temperature & pressure gauges are factory

mounted in the in/out header except for residential

boilers, Models 133 and 181-401. On these models

the temperature & pressure gauge is shipped loose for

field installation, and located in the outlet water con-

nection. All fittings required to mount gauge to piping

system are supplied by others.

Table H: Maximum and Minimum Flow Rates

Advertising