Raypak RAYTHERM 133-4001 User Manual

Page 39

Advertising
background image

39

2. Lift burners from slotted spacer and slide from ori-

fices. Clean with a wire brush.

3. Clean orifice(s) as necessary.

Pilot Removal and Cleaning

1. Disconnect pilot tubing at pilot and sensor/igniter

wire. Remove screws holding pilot bracket to burn-

er tray.

2. Remove pilot and bracket, clean pilot of debris,

small bugs, etc., with wire or small brush.

3. Replace pilot, pilot tubing, sensor ignition wires

and check for leaks.

High Limit or Tankstat Removal

1. Turn off electrical power.

NOTE: If the heat exchanger is sooted badly, the

burner hold-down bracket and spacer can become

distorted from direct flame impingement and this

usually necessitates replacement of these parts.

2. Remove front inspection panel.

3. Remove wires to high limit and loosen screws

holding high limit to cabinet.

4. Remove wedge clip holding sensing bulb in con-

trol well.

5. Remove high limit and install a new one.

6. Check control operation before leaving job.

Heat Exchanger Removal

1. Shut water, gas and electricity off, close valves

and relieve pressure, remove relief valve. Remove

side inspection panels.

2. Remove top holding screws.

3. Remove draft diverter, lift and remove top and flue

collector on stack type models. Remove inspec-

tion panels.

4. Loosen bolts and disconnect flange nuts on in/out

header, loosen union(s) at gas pipe, and slide boil-

er away from piping until studs clear the heater.

IN/OUT

HEADER

HIGH LIMIT

ELECTRICAL

JUNCTION BOX

REDUNDANT

SAFETY

SHUT-OFF

VALVE

MANUAL GAS VALVE

MAIN GAS VALVE

SEDIMENT TRAP

Fig. 52: Model 2100–4001 Boiler Illustration