Outdoor boilers, High-wind conditions (outdoor units only), Combustion and ventilation air – Raypak RAYTHERM 133-4001 User Manual

Page 8: Indoor units only), High-wind conditions (outdoor units only)8, Combustion and ventilation air (indoor units only)

Advertising
background image

8

NOTE: Combustible floor shield is required when

boiler is to be installed on a combustible surface.

(See ordering information in Table B)

NOTE: Servicing Clearances: Provide at least 24"

(Models 133-1826), 48" (Models 2100-4001) in front

of unit for removal and servicing of the Controls &

Burner Tray. Provide at least 18" on side opposite

water connections for deliming of Heat Exchanger

Tubes.

NOTE: The boiler shall be installed in a space large

in comparison to the size of the boiler. Large space

is defined as having a volume at least sixteen (16)

times the total volume of the boiler.

Table D: Reduction of Clearances to Protected

Surfaces

Derived from National Fuel Gas Code, Table 6.2.3(b)

Outdoor Boilers

These boilers are design certified for outdoor installa-

tion. Boilers must not be installed under an overhang

within three (3) feet from the top on the boiler. Three

(3) sides must be open in the area under the over-

hang. Roof water drainage must be diverted away

from the boilers with the use of gutters.

The point from where the flue products exit the boiler

must be a minimum of four (4) feet below, four (4) feet

horizontally from or one (1) foot above any door, win-

dow or gravity inlet to a building. The top surface of the

boiler shall be at least three (3) feet above any forced

air inlet, or intake ducts located within ten (10) feet hor-

izontally.

High-Wind Conditions (Outdoor

Units Only)

In areas where high winds are frequent, it may be nec-

essary to locate the boiler a minimum of 3' from high

vertical walls, or install a wind break so the boiler is not

in direct wind current.

Combustion and Ventilation Air

(Indoor Units Only)

The boiler must have both combustion and ventilation

air. Minimum requirements for net free air supply

openings are 12 inches from ceiling for ventilation and

12 inches from the floor for combustion air as outlined

in Z223.1 - latest edition and any local codes that may

have jurisdiction.

Fig. 3: Minimum Distances to Building Openings from

Where Flue Products Exit the Boiler

Advertising