Venting – Raypak RAYTHERM 133-4001 User Manual

Page 9

Advertising
background image

9

a. All Air From Inside The Building:

Each opening shall have a minimum net free

square inches as noted in Table E.

b. All Air From Outdoors:

When air is supplied directly from outside of build-

ing, each opening shall have a minimum net free

square inches as noted in Table F.

CAUTION: Combustion air must not be

contaminated by corrosive chemical fumes which

can damage the boiler and void the warranty.

Model

Sq. Inches

Model

Sq. Inches

133

136

1125

1125

182/181

181

1223

1223

260/261

264

1336

1337

330/331

334

1468

1467

400/401

399

1631

1630

514

512

1826

1826

624

627

2100

2100

724

726

2500

2499

824

825

3001

3000

962

962

3500

3500

4001

4000

Model

Sq. Inches

Model

Sq. Inches

133

34

1125

282

182/181

46

1223

306

260/261

66

1336

335

330/331

84

1468

367

400/401

100

1631

408

514

128

1826

457

624

157

2100

525

724

182

2500

625

824

207

3001

750

962

241

3500

875

4001

1000

Table E: Minimum Net Free Air from Inside Building

Table F: Minimum Net Free Air from Outside Building

Venting

Outdoor Installations

Model 133

1. Remove the front (4) screws.

2. Line up outdoor top vent opening over heater vent

opening.

3. Lower outdoor top onto unit lining up slots in the

outdoor top with screw holes in jacket top.

4. Reinstall (5) screws to secure jacket top and out-

door top to unit.

Models 181-401 & 182-400

Outdoor Top Installation

Fig. 4: Installing Outdoor Top—Model 133

(Part of heater)

Fig. 5: Installing Outdoor Top—Models 181-401 & 182-

400