LIGHTING INSTRUCTIONS FOR BOILERS WITH ELECTRONIC IGNITION (IID)
For Models with Manual Gas Valves

FOR YOUR SAFETY READ BEFORE OPERATING

WARNING: If you do not follow these instructions exactly, a fire or explosion may result causing
property damage, personal injury or loss of life.

A. This appliance is equipped with an ignition device which

automatically lights the pilot. Do not try to light the pilot
by hand.

B. BEFORE OPERATING smell all around the appliance

area for gas. Be sure to smell next to the floor because
some gas is heavier than air and will settle on the floor.
WHAT TO DO IF YOU SMELL GAS

*

Do not try to light any appliance.

*

Do not touch any electric switch; do not use any phone
in your building.

*

Immediately call your gas supplier from your neighbor’s
phone. Follow the gas supplier’s instructions.

*

If you cannot reach your gas supplier, call the fire de-
partment.

C. Use only your hand to push in or turn the gas control

knob. Never use tools. If the knob will not push in or turn
by hand, do not try to repair it, call a qualified service
technician. Force or attempted repair may result in a fire
or explosion.

D. Do not use this appliance if any part has been under

water. Immediately call a qualified service technician to
inspect the appliance and to replace any part of the
control system and any gas control which has been
under water.

OPERATING INSTRUCTIONS

For Honeywell gas valve: Turn gas control knob
counter-clockwise

from “OFF” until it

stops. Push in gas control knob and continue
rotating counter-clockwise

to “ON”

position. Make sure knob rests against stop.

For Honeywell gas valve (Models 40# only):

Turn gas control knob counter-clockwise to “ON”.

9.

Replace boiler door panel.

10. Turn on all electrical power to the appliance.
11. Set thermostat to desired setting.
12. If the appliance will not operate, follow the instructions

“To Turn Off Gas To Appliance” and call your service
technician or gas supplier.

HONEYWELL
GAS CONTROL
KNOB SHOWN
IN "ON" POSITION

GAS INLET

ROBERTSHAW
GAS CONTROL
KNOB SHOWN
IN "ON" POSITION

GAS INLET

TO TURN OFF GAS TO APPLIANCE

1.

Set the thermostat to the lowest setting.

2.

Turn off all the electrical power to the appliance if service
is to be performed.

3.

Remove door panel.

4.

For Robertshaw gas valve: Turn gas control knob
clockwise

to “OFF”.

For Honeywell gas valve (all models except 40#):

Turn gas control knob clock-wise

to “OFF”.

Make sure knob rests against stop.
For Honeywell gas valve (Models 40# only):
Push in gas control knob slightly and turn clockwise

to “OFF”.

5.

Replace heater door panel.

GAS CONTROL KNOB
SHOWN IN "ON"
POSITION

GAS INLET

1.

STOP! Read the safety information above.

2.

Set the thermostat on the lowest setting.

3.

Turn off all electrical power to the appliance.

4.

This appliance is equipped with an ignition device which
automatically lights the pilot. Do not try to light the pilot
by hand.

5.

Remove boiler door panel.

6.

For Robertshaw gas valve: Turn gas control knob
clockwise

to “OFF”.

For Honeywell gas valve (all models except 40#):
Turn gas control knob clockwise

to “OFF".

Make sure knob rest against stop.
For Honeywell gas valve (Models 40# only):
Push in gas control knob slightly and turn clockwise

to “OFF”. Knob cannot be turned to “OFF”

unless knob is pushed in slightly. Do not force.

7.

Wait five (5) minutes to clear out any gas. Then smell
for gas, including near the floor. If you smell gas, STOP!
Follow “B” in the safety information above. If
you do not smell gas, go to the next step.

8.

For Robertshaw gas valve: Turn gas control knob
counter-clockwise

to “ON”.

Advertising