Warning – Roberts Gorden CTCU 27 User Manual

Page 10

Advertising
background image

COMBAT

®

CTCU U

NIT

H

EATER

I

NSTALLATION

O

PERATION

AND

S

ERVICE

M

ANUAL

4

Figure 1: Installation Clearances and Clearances to Combustibles

WARNING

Fire Hazard

Some objects will catch fire or explode when placed

close to heater.
Keep all flammable objects, liquids and vapours the

required distance away from the heater.
Failure to follow these instructions can result in death,

injury or property damage.

50 cm**

10 cm

30 cm

15 cm

Clearances to Combustibles

Wall

Terminal

Roof Terminal

Air

Intake

Flue

15 cm

2.5 - 3.5 m*

3 m

25 cm

Installation Clearances

3 m

Roof Terminal

If installed at low levels where individuals can come in contact with hot heat exchanger components,
adequate guarding must be provided.

All distances are minimum clearance requirements for service access, air flow and safety.

The heater must always be installed at least 1.8 m above the floor.
The flue pipe must have clearance from combustibles by 5 cm.

* Heaters may be mounted at a higher level if destratification

fans are installed.

**80 cm is necessary to service

heater.