SECTION 5: H

EATER

I

NSTALLATION

7

SECTION 5: HEATER INSTALLATION

5.1 General

Heaters are designed for installation above 1.8 m.
These heaters must be installed within the heated
space. Duct delivery systems are not permitted with
axial fans. When handling or supporting the heater
from below, ensure that the weight is taken at the
support points.

5.2 Shelf Mounting and Suspension

For typical suspension, See Page 7, Figure 2.

5.3 Wall Mounting

For typical suspension, See Page 8, Figure 3.
Heaters blowing parallel to the wall can only be
installed with the service door away from the wall.

The wall mounting brackets must be attached to a
suitable wall through all mounting holes. Screw
sizes less than M10 may not be used. In order for
the wall mounting brackets to adequately carry the
weight of the heater, it must be installed with best
building practice.

Figure 2: Suspension Methods

Existing cabinet screws must be re-used.

WARNING

Crush Hazard

Use 10 mm steel drop rod

minimum.

Failure of the supports can

result in death, injury

or property damage.

Cone Point

Set Pin

Window

Clamp

Unistrut

10 mm

Steel

Drop Rod

Nut

Washer

Riv

Nut

Support Points

Ensure all suspension hardware

is torqued to a minimum

of 27 Nm (20 ft lbs).

NOTE: For vertical installations, use the mounting points on the rear of the unit.

10 mm

Steel

Drop Rod

Washer

Nut

Unistrut

Channel Nut

Shelf Mounting

Brackets

Description

Part Number

Qty.

Shelf Mounting Bracket
Kit

11111510K

Shelf Mounting Bracket (2)

111111510

2

Screw #10 x 1/2"
Type AB Phil HWH Z (2)

94311008

2