SECTION 14: T

ROUBLESHOOTING

23

14.2 Troubleshooting For Automatic Ignition Burner Systems

If problems persist, contact

Roberts-Gordon Ltd. at

Tel: +44 (0) 1902 498733

www.rg-inc.com

Heater Operating

TROUBLESHOOT ENDS. No

Trace fault in supervision

system. See Section 14.3.

Yes

Is red lockout light on?

No

Is the flame current at

least 1 µAmp DC when

the flame lights?

Ignition control faulty;

replace.

See Section 15.6.

Is HT lead okay and

connected?

Is spark electrode okay?

Yes

Replace valve.

Is the gas valve operating?

To test valve,

See Section 14.4.

No

Does the flame light?

No

Yes

Wait 30 - 40 seconds.

Is ignition spark operating? No

Yes

Flue fan faulty; replace

Burner control faulty or plug

in connections faulty. Repair

or replace as necessary

Check for too much flue/air inlet

duct. Check for blockage in

combustion air circuit.

Check for faulty air pressure

switch. See Section 15.5.

Does air pressure switch

change over?

No

Yes

Turn on controls.

Is 230 V supply at fan

connections?

Does flue fan run?

No

Are external controls on?

No

Yes

Yes

Is red lockout light on?

No

Yes

Press in lockout reset button

on rear of heater or remote

reset button if fitted.

Turn on supplies.

Are gas & electrical

supplies on?

Yes

Start

No

Yes

No

Yes

WARNING

Electrical Shock Hazard

Do not touch ignition components.

Voltage from ignition components is high.

Failure to follow these instructions can

result in death or electrical shock.

For your safety and optimum heater performance,
use only ROBERTS GORDON

®

replacement parts.

Conduct Commissioning procedure as shown
on Page 15, Section 10
.