14.4 Troubleshooting for Solenoid Valves

14.5 Troubleshooting for Main Fan

Valve faulty.

Replace with one of

correct type.

Fault elsewhere.

If problems persist, contact

Roberts-Gordon Ltd. at

Tel: +44 (0) 1902 498733

www.rg-inc.com

Valve Operating

TROUBLESHOOT ENDS.

No

Yes

Valve or ignition control

faulty. Replace with

one of correct type.

Does gas pressure at

outlet of valve return to zero or

lower when valve turns off?

No

Yes

Does gas pressure at outlet

of the valve rise when

valve turns on?

No

Yes

Is gas pressure at inlet of the

valve correct for gas type?

Note pressure found.

No

Yes

START

If problems persist, contact

Roberts-Gordon Ltd. at

Tel: +44 (0) 1902 498733

www.rg-inc.com

Fan Operating

TROUBLESHOOT ENDS. No

Fan motor faulty.

Replace with correct type.

Is there 230 V between

terminals L

1

and N?

Replace fan

delay thermostat.

Replace fan

delay thermostat.

Is power supply 230 V at

terminals T

1

to N?

No

Yes

START

Does fan turn on and

off while burner is firing

continously?

No

Yes

Does fan run

automatically?

No

Yes

Yes

For your safety and optimum heater performance, use only genuine ROBERTS GORDON

®

replacement

parts.
Conduct Commissioning procedure as shown

on Page 15, Section 10.