SECTION 13: CONVERSION BETWEEN GASES

13.1 General

Conversion between gases will require a change of
burner injectors and the gas valve re-commissioning
to the new conditions.
13.2 Burner Conversion

Conversion of the burner assembly from one gas to
the other is the same for all types of heaters.

1. Remove the burner compartment cover as

shown on Page 27, Section 15.2.

2. Remove the 4 screws holding the manifold and

pull out the manifold.

3. Remove inshot burners by rotating them and

sliding out the bracket.

4. Remove the main burner injectors.

5. Replace with the injectors for the new gas

ensuring a gas tight seal.

6. Refit all components in reverse order.

13.3 Gas Valves

All gas valves used on the CTCU have pressure
regulators that may be set to operate on natural gas
or LPG.
Conversion is carried out by re-setting the burner
pressure to the value in the data table during
commissioning. See Page 6, Section 4.3.
Ensure that the gas inlet pressure to the heater is
correct for the new gas, and that the gas supply has
been purged of the old gas.