Figure 9: Automatic Burner Control Box Sequence

Figure 10: Gas Valve for Heater Models 7 - 32

Burner sequence for Honeywell S4565C

Flame Signal

Start Gas Valve

Ignition Spark

Supply 230 V

CLOSE

DOWN

RUN

START

ts = 10 seconds

Signals Output By Control

Required Incoming Signals

Flue Fan

Pressure Switch P

C

NO

NC

30 Sec. Purge*

*Purge time begins at pressure switch change over.

If at any stage the flame fails, the control will go into "lockout". The red light inside the RESET
switch will illuminate and the control will need to be manually reset before any further start
attempt can be made.

Regulator

(Under Cover)

Inlet Pressure

Gas Inlet

Ignition Control

(Plugs into Gas Valve)

12 Cable Connector

Outlet Pressure

Screw

Ignition

Output

Flame

Probe

Connection

End View