Canadian ecoenergy configuration – Retrotech DM-2A User Manual

Page 46

Advertising
background image

38

Retrotec Energy Innovations, Ltd.

DM-2A Mark II 2008-02-22

To perform your CGSB 149.10 standards test procedure, follow these steps:

1. Assess and measure the Envelope Area as specified in the standard.

2. With your gauge on and running and from the main operation screen, press the

M

Ode

keypad button to set your gauge to EqLA/Area mode.

For the EqLA/Area mode to be available, it must be enabled. To enable a mode use options

in the Setup screen. A mode is enabled when it is set to a value other than off.

3. Press the e

nteR

keypad button and input the envelope area value according to

your measurements.

4. Conduct door-fan test at 50 Pa or as specified in the standard.

5. Use the @ p

ReSSuRe

keypad button to display the Flow @ 25.0 Pa and the EqLA @

10.0 Pa.

6. Results for EqLA and NLA (=EqLA/Area) may be read directly from your gauge.

7. Your CGSB 149.10 standards test procedure is complete.

For more information on standards used by the Canadian General Standards Board, visit

http://pwgsc.gc.ca/cgsb/home/index-e.html

.

Canadian ecoENERGY Configuration

The Canadian ecoENERGY Program requires reading of EqLA at 10 Pa and air-changes at 50 Pa.

Most test technicians prefer using imperial units but metric units are simply to apply. Your DM-
2A gauge will provide these values automatically without doing a multipoint test or you can
use Retrotec’s Door-Fan 3.0 software to perform the test manually or even automatically with
Retrotec model Q systems such as the Q46, Q4E and Q56.

DM-2A Mark II Dual-Channel Pressure Gauge

User Manual

A: