To configure your gauge for the Dansk Standard for thermal performance of buildings,

determination of air permeability of buildings, fan pressurization method, apply the following
settings:

DS/EN 13829 Configuration

Mode Setup

Pressure

Pa

Flow

m

3

/h

@ 50.0 Pa

EfLA

Off

EqLA

Off

Air Changes

/h

@ 50.0 Pa

Flow per Area

cm

3

/h/m

2

@ 50.0 Pa

EqLA per Area

Off

Velocity

Off

Velocity Flow

Off

(Other Settings)

n

0.65

Power Down Hour

2

Area

m

2

Volume

m

3

European

No

Sig Figs

2.5

Reverse Mode

No

DS/EN 13829 is a multi-point test. However, the DM-2A mark II can also provide for

quick single-point checks of the enclosure. To perform a single-point test, follow these
steps:

1. Assess and measure the Envelope Area as specified in the standard.

2. Assess and measure the Net Floor Area as specified in the standard.

3. Assess and measure the Internal Volume of the building as specified in the standard.

4. With your gauge on and running and from the main operation screen, press the M

Ode

keypad button to set your gauge to the Air Chg mode.

5. Press the e

nteR

keypad button and input the Internal Volume as measured in step 3.

6. Press the M

Ode

keypad button to display screen to view the Flow/Area mode.