Warning – Roberts Gorden 125 User Manual

Page 14

Advertising
background image

UHD L

OW

P

ROFILE

D

UCT

F

URNACE

I

NSTALLATION

O

PERATION

AND

S

ERVICE

M

ANUAL

6 of 47

SECTION 4: CLEARANCES TO COMBUSTIBLES

4.1 Required Clearances to Combustibles

Clearances are the required distances that
combustible objects must be away from the heater
to prevent fire hazard. Combustible material that
may catch fire include common items such as wood,
paper, rubber, fabric, etc. Maintain clearances to
combustibles at all times for safety.
Clearances for all heater models are located on the
serial plate of the heater and throughout the manual.
Check the clearances on the serial plate to make
sure the product is suitable for your application and
the clearances are maintained. Read and follow the
safety guidelines below:

• Keep gasoline or other combustible material

including flammable objects, liquids, dust or
vapors away from this heater or any other
appliance.

• The stated clearances to combustibles

represents a surface temperature of 90° F
(50° C) above room temperature. Building
materials with a low heat tolerance (such as
plastics, vinyl siding, canvas, tri-ply, etc.) may be
subject to degradation at lower temperatures. It
is the installer's and owner's responsibility to
assure that adjacent materials are protected
from degradation.

• Consult local Fire Marshall, Fire Insurance

Carrier or other authorities for approval of
proposed installation when there is a possibility
of exposure to combustible airborne materials or
vapors.

4.2 Clearances to Combustibles

Clearances must be as indicated

on Page 6, Figure

3. If clearances to combustibles are not indicated,
then installation clearances apply.

Figure 3: Clearances to Combustibles

WARNING

Fire Hazard

Keep all flammable objects, liquids and
vapors the minimum required clearances to
combustibles away from heater.

Some objects will catch fire or explode when
placed close to heater.

Failure to follow these instructions can result
in death, injury or property damage.

Clearance to Vent: 2" (5 cm)

*18" (46 cm) minimum is necessary for
servicing.

Advertising
This manual is related to the following products:

75, 100