SECTION 6: DUCT HEATER INSTALLATION

6.1 General

To connect the inlet and outlet ducts to the heater,
Duct-Mate or similar flanges may be slid over the
duct connector flanges supplied on the unit and
secured with screws. The connection to the duct
then can be made using the Duct-Mate clips. The
ducts must have removable access panels
upstream and downstream of the heater. These
panels must be of appropriate size and placement
so that smoke or reflected light could be observed to
indicate the presence of leaks in the heat
exchanger. Covers for these openings should be
sealed to prevent leakage.

Any transition into the inlet of the heater should be
smooth, with a taper of no more than 15 degrees. If
elbows are required, they should be of either broad
radius or fitted with properly designed air turns.
Consult a professional to ensure air turns are
properly designed.

The heater must be installed on the positive
pressure side of the circulating air blower. Air flow
through the heater must be as shown

on Page 9,

Figure 4 and may not be reversed. The air flow must
be adjusted such that it is within the acceptable
range shown on

Page 9, Section 6.1.3. The

minimum inlet duct lengths shown

on Page 9,

Section 6.1.1 should be observed. Pressure drop
through the heat exchanger at various air flows is
given

on Page 9, Section 6.1.2.

Figure 4: Air Flow Direction

6.1.1 Minimum Inlet Duct Length

6.1.2 Temperature Rise and Pressure Drop Ranges

6.1.3 Air Flow and Temperature Rise Ranges

AIR FLOW

OUTLET DUCT

INLET DUCT

Model

Duct Length

Duct Size (W X H)

UHD[X][S] 75

32" (81 cm)

16 3/4" x 15 7/8" (43 cm x 40 cm)

UHD[X][S] 100 &125

37" (94 cm)

21 3/4" x 15 7/8" (55 cm x 40 cm)

UHD[X][S] 75

UHD[X][S] 100

UHD[X][S] 125

Airflow

(CFM)

Temperature

Rise (°F)

Pressure Drop

(in wc)

Airflow

(CFM)

Temperature

Rise (°F)

Pressure Drop

(in wc)

Airflow

(CFM)

Temperature

Rise (°F)

Pressure Drop

(in wc)

850

68

0.06

950

78

0.05

1,020

92

0.06

1,200

48

0.10

1,500

50

0.18

1,650

57

0.14

1,625

36

0.16

2,500

31

0.28

2,340

41

0.27

1,965

30

0.22

3,000

26

0.39

3,480

28

0.56

2,450

24

0.31

3,300

24

0.46

4,240

23

0.80

2,650

22

0.36

3,660

22

0.55

4,750

20

0.98

Model

Rate

Air Flow

Temperature Rise

(Btu/h)

Minimum (CFM)

Maximum (CFM)

Minimum (°F)

Maximum (°F)

UHD[X][S] 75

75,000

850

2,650

22

68

UHD[X][S] 100

100,000

950

3,660

22

78

UHD[X][S] 125

125,000

1,020

4,750

20

92