Figure 17: Manual Reset Limit Switch

12.3 Lighting Instructions

12.3.1 To Turn On Heater

1. Ensure that the electrical and gas supplies to

the heater are on. Check that the on site
controls are "ON".

IMPORTANT: The thermostat setting must be above
the ambient temperature for the heater to operate.

2. The automatic firing sequence will begin as

described

on Page 27, Figure 15. The heater

will now operate automatically under the control
of the on site controls.

12.3.2 To Turn Heater Off

Set the thermostat to the "OFF" position.
The burner will turn off immediately.
To restart, turn the thermostat above room
temperature.

12.4 Simple Troubleshooting

Some possible reasons for the heater not operating
are:

1. Gas supply not "ON".

2. Electricity supply not "ON".

3. The time and/or temperature controls are not

"ON".

4. A limit switch may have operated. This may be

caused by an interruption of the electrical
supply, failure of the distribution fan or vent or
heat exchanger blockage.

If a temperature limit switch persistently trips, there
is a fault which must be investigated by a contractor
qualified in the installation and service of gas-fired
heating equipment.

12.4.1 Simple Troubleshooting (Burner Faults)

If the burner fails to ignite for any reason, it will retry
for ignition (four trials total). After four unsuccessful
ignition trials, the control will put the heater into
lockout for one hour.

Lockout should not occur during normal operation of
the heater and indicates there is a fault condition
which must be corrected. There is an LED light on
the ignition control that flashes codes to assist in
fault correction.

See Page 30, Figure 18 for LED

indication codes.

Figure 18: LED Diagnostic Codes

Reset Button

To reset manual reset limit switch, press reset
button. NOTE: To reset, the switch must be cool.

Description

Part Number

Manual Reset Limit Switch

90412106

LED INDICATION FAULT MODE

Slow Flash

Normal Operation - No call for heat.

Fast Flash

Normal Operation - Call for heat.

2 Flashes

Ignition Lockout - No flame detected.

3 Flashes

Airflow Fault - Pressure switch open or closed.

4 Flashes

Temperature Limit or
Manual Reset Limit Switch Open

5 Flashes

Flame Sense Error - Gas valve not energized.

Steady On

Internal Control Failure