background image

UHD L

OW

P

ROFILE

D

UCT

F

URNACE

I

NSTALLATION

O

PERATION

AND

S

ERVICE

M

ANUAL

40 of 47

15.2 Burner Compartment

15.2.1 Burner Injectors

Remove flexible
air duct from spigot

Viewing port
for flame probe

Flame Probe

Burner
Compartment
Cover

Ignition Electrode

Remove screws and
pull off burner cover

The burner compartment is a sealed
compartment. Following any work,
re-seal the compartment with the
gas pipe rubber seal fully in place
and all screws fitted and tight.

NOTE: Flexible duct only applies for
model UHDS.

MODEL

UHD[X][S] 75

UHD[X][S] 100

UHD[X][S] 125

Orifice Quantity

5

6

7

Natural Gas (G20)

Orifice Marking

49

46

46

P/N

91930049

91930046

91930046

Propane (G31)

Orifice Marking

1.15 mm

1.25 mm

1.25 mm

P/N

91930115

91930125

91930125

Ensure gas tight fitting
of injectors.

Ensure correct alignment
with burners.

Ensure all pipe joints are
gas tight.