CONNECTIONS – PLUMBING

38

Solar Circuit Relief Valve
Ensure the outlet of the solar circuit relief valve is facing toward the rear of the
water heater installation. A copper drain line must be fitted to the relief valve to
carry the discharge clear of the water heater. Connect the drain line to the relief
valve using a compression nut and brass or copper olive. The pipe work from
the relief valve to the drain should be as short as possible and fall all the way
from the water heater with no restrictions. It should have no more than three
right angle bends in it. Use DN15 pipe.

The outlet of the drain line must be in such a position that flow out of the pipe
can be easily seen (refer to AS/NZS 3500.4) - but arranged so hot water
discharge will not cause injury, damage or nuisance. The drain line must
discharge at an outlet or air break not more than 9 metres from the relief valve.

In locations where water pipes are prone to freezing, the drain line must be
insulated and not exceed 300 mm in length. In this instance, the drain line is to
discharge into a tundish through an air gap of between 75 mm and 150 mm.

EXPANSION CONTROL VALVE
Local regulations may make it mandatory to install an expansion control valve
(ECV) in the cold water line to the water heater. In other areas, an ECV is not
required unless the saturation index is greater than +0.4 (refer to

“Water

Supplies”

on page 76). However, an ECV may be needed in a corrosive water

area where there are sufficient quantities of silica dissolved in the water.

The expansion control valve must always be installed after the non return valve
and be the last valve installed prior to the water heater

(refer to diagram on

page

36

)

. A copper drain line must be run separately from the drain of the relief

valve.