7

NOTE:

1. All dimensions are from the surfaces of all tubes, couplings, elbows, tees and crosses.
2. Clearances B, C and D can be reduced by 50% after 25' (7.5 m) of tubing downstream from
where the combustion chamber and the tube connect.

FIGURE 9: 2-FOOT DECO GRILLE

(inches)

(centimeters)

Model

A

B

C

D

A

B

C

D

CRV-B-2

4

12

48

12

11

31

122

31

CRV-B-4

4

12

48

12

11

31

122

31

CRV-B-6

4

12

48

12

11

31

122

31

CRV-B-8

4

12

48

12

11

31

122

31

CRV-B-9

4

18

56

18

11

46

143

46

CRV-B-10

4

18

56

18

11

46

143

46

CRV-B-12

4

18

56

18

11

46

143

46

CRV-B-12A

4

18

56

18

11

46

143

46

A

B

C

D

FIGURE 10: BARRIER SHIELD

(inches)

(centimeters)

Model

A

B

C

D

A

B

C

D

CRV-B-2

4

12

12

12

11

31

31

31

CRV-B-4

4

12

12

12

11

31

31

31

CRV-B-6

4

12

12

12

11

31

31

31

CRV-B-8

4

12

12

12

11

31

31

31

CRV-B-9

- UNAPPROVED -

- UNAPPROVED -

CRV-B-10

- UNAPPROVED -

- UNAPPROVED -

CRV-B-12

- UNAPPROVED -

- UNAPPROVED -

CRV-B-12A

- UNAPPROVED -

- UNAPPROVED -

C

A

B

D

FIGURE 11: PROTECTIVE GRILLE

(inches)

(centimeters)

Model

A

B

C

D

A

B

C

D

CRV-B-2

4

20

48

20

11

51

122

51

CRV-B-4

4

20

48

20

11

51

122

51

CRV-B-6

4

20

48

20

11

51

122

51

CRV-B-8

4

20

48

20

11

51

122

51

CRV-B-9

4

36

60

36

11

92

153

92

CRV-B-10

4

36

60

36

11

92

153

92

CRV-B-12

4

36

60

36

11

92

153

92

CRV-B-12A

4

36

60

36

11

92

153

92

A

B

C

D

Advertising