Roberts Gorden CoRayVac CRV-B-6 User Manual

Page 71

Advertising
background image

SECTION 17: G

ENERAL

S

PECIFICATIONS

65

SECTION 17: GENERAL SPECIFICATIONS
17.1 Material Specifications

17.1.1 Reflectors

.024

Aluminium (Optional - 024 Stainless Steel Type 304).

17.2 Heater Specifications

17.2.1 Ignition

Fully Automatic, Three-Try, Direct Spark, Electronic
Ignition Control, 100% Safety Shut-Off.

17.3 Suspension Specifications

Hang heater with materials with a minimum working
load of 75 lbs (33 kg). See Page 17, Figure 14.

17.4 Controls Specifications

Time switches, thermostats, etc. can be wired into
the electrical supply. External controls supplied as an
option.

General Specifications for CRV-Series heaters are as follows:

*See Page 4, Section 3 for clearances to combustibles.

PIPE CONNECTION:
1/2" NPT

DIMENSIONS:
Vent Connection Size: 4" (10 cm) or 6" (15 cm)
Outside Air Connection Size: 4" (10 cm)
Refer to figure above for dimensional information.

GAS INLET PRESSURE:
Natural Gas: 4.5

"

wc Minimum 14.0

"

wc Maximum

LP Gas: 10.5

"

wc Minimum 14.0

"

wc Maximum

ELECTRICAL RATING:
120 V - 60 Hz, 0.3 A

Reflector

Length "A"

20"

(51 cm)

10"

(24.4 cm)

6 1/2"

(16 cm)

10 3/4"

(27 cm)

4"

(10 cm)

6 7/8"

(17 cm)

3 1/2"

(9 cm)

7 5/8"

(19 cm)

14 1/4"

(36 cm)

9 1/2"

(24 cm)

5/32"

(.4 cm)

Heat Input Rate

Length “A”

Recommended Minimum

Mounting Height*

Model

(Btu/h) x (1000)

Minimum

Maximum

Spot Heating

CRV-B-2 (NG only)

20

10' (3 m)

20' (6.1 m)

8' (2.4 m)

CRV-B-4

40

12.5' (3.8 m)

25' (7.6 m)

8' (2.4 m)

CRV-B-6

60

20' (6.1 m)

35' (10.7 m)

8' (2.4 m)

CRV-B-8

80

20' (6.1 m)

45' (13.7 m)

10' (3 m)

CRV-B-9

90

25' (7.6 m)

50' (15.2 m)

10' (3 m)

CRV-B-10

100

30' (9.1 m)

60' (18.3 m)

15' (4.5 m)

CRV-B-12A (NG only)

110

35' (10.7 m)

70' (21.3 m)

15' (4.5 m)

CRV-B-12 (LP only)

120

35' (10.7 m)

70' (21.3 m)

15' (4.5 m)

Advertising
This manual is related to the following products: