FIGURE 21: Duct Sizing

10.3 Outside Air Blower Internal Wiring

FIGURE 22: Outside Air Blower Internal Wiring Diagram

Outside Air System Design Requirements:

Blower Performance (90707501):
112 Flow Units
One outside air blower is required per each EP-100 or
EP-200 series pump and two outside air blowers may
be required for each EP-300 series pump. Outside air
blowers cannot be shared between two separate CRV-
Series systems.

Duct Design Rules:

- System should be designed so that the blower is

positioned closest to the highest flow
requirements (end vents).

- When a duct is carrying more than 40 flow units, it

must be at least 6" (15 cm) diameter.

Pressurized Systems

- 6" (15 cm) diameter duct must not exceed 120'

(36 m) total per system.

- 4" (10 cm) diameter duct must not exceed 120'

(36 m) per radiant branch.

Non Pressurized

- 6" (15 cm) diameter duct must not exceed 90'

(27 m) maximum 100 flow units

- 4" (10 cm) diameter duct must not exceed 90'

(27 m)

- Elbows are equivalent to 10' (3 m) of duct length.

L

MOTOR

M

N

BLK

WHT

T1

T3

T2

C

NO

BLU

BLU

BLOWER

PRESSURE

SWITCH

The outside air blower is shipped with the
blower manufacturer’s standard internal wiring.
For use with ROBERTS GORDON

®

heaters,

the outside air blower must be rewired with
existing wires by the electrical contractor. See
diagram.

The internal 24 V transformer provided will not
be used and can be discarded.