Caution, System control, Ground – Roberts Gorden CoRayVac CRV-B-6 User Manual

Page 58

Advertising
background image

CRV-S

ERIES

I

NSTALLATION

, O

PERATION

AND

S

ERVICE

M

ANUAL

52

FIGURE 34: External Wiring Diagram EP-203 or EP-303 208 - 230 V (or 460 V) 3 Ø Pump

System Control

R

R

R

R

PS 2

PS 1

24 VAC
COM

24 VAC
COM

PS 1

PS 2

W

W

W

W

24 VAC

120 V
1 Ø
60 Hz

Ground

G

L

N

120 V
1 Ø
60 Hz

PUMP 2

PUMP 1

POWER
SUPPLY

N L

Z1

Z2

Z3

Z4

N

N

N

N

L

L

L

L

All burners must be
connected to Ground
(Not shown)

Zone 1 Zone 2 Zone 3 Zone 4

EP-203 or

EP-303 3 Ø

Pump

N L

L

N

208 - 230 V
(or 460 V)
3 Ø
60 Hz

Individual supply
for pump rated for
total full load current.
See Pump Specification
Section for details.

EP-203 or

EP- 303 3 Ø Pump

M

L1

L3

L2

The power supply for the
pump must be separate
from the controller supply

TWO PUMP SYSTEM (optional)
Pump 1 may be used for all zones.
Pump 2 may be used to control zone 3
and/or zone 4. Refer to Pump 1 for configuration.

Motor Contactors
P/N 10050011
P/N 10050012

Low voltage thermostats

located in heated zone

Zone

1

Zone

2

Zone

4

Zone

3

Pressure
switch
located at
Pump 2

Pressure
switch
located at
Pump 1

CAUTION

Product Damage Hazard

Do not directly connect control relay terminals
to pump motor.

Failure to follow these instructions can result
in product damage.