Caution – Roberts Gorden CoRayVac CRV-B-6 User Manual

Page 9

Advertising
background image

SECTION 2: I

NSTALLER

R

ESPONSIBILITY

3

SECTION 2: INSTALLER RESPONSIBILITY
The installer is responsible for the following:

• To ensure the system is designed in accordance

with the parameters of the CRV-Series

Design

Manual (P/N 127500NA).

• To install the heater, as well as the gas and

electrical supplies, in accordance with applicable
specifications and codes. Roberts-Gordon LLC
recommends the installer contact a local Building
Inspector or Fire Marshal for guidance.

• To use the information given in a layout drawing

and in the manual together with the cited codes
and regulations to perform the installation.

• To install the heater in accordance with the

clearances to combustibles requirements.

• To furnish all needed materials not furnished as

standard equipment.

• To plan location of supports.
• To provide access to burners on all sides for

servicing or burner removal.

• To provide the owner with a copy of this

Installation, Operation and Service Manual.

• To never use heater as a support for ladder or

other access equipment and to never hang or
suspend anything from heater.

• To ensure there is adequate air circulation around

the heater and to supply air for combustion,
ventilation and distribution in accordance with
local codes.

• To safely and adequately install heater using

materials with a minimal working load of 75 lb
(33 kg).

• To ensure the heater is placed in an approved

application.

2.1 Wall Tag

A laminated wall tag is available for the heater as a
permanent reminder of the safety instructions and
the importance of the required clearances to
combustibles. Please contact Roberts-Gordon LLC
or your ROBERTS GORDON

®

independent

distributor to obtain the wall tag. Affix the tag by
peeling off the backing of the adhesive strips on the
rear surface and position the tag on a wall near the
CRV-Series heater (e.g. thermostat or controller).
A copy of the wall tag (P/N 91037912) is illustrated on
the back cover. For an immediate solution, you may
affix this copy on the wall near the heater.
Know your model number and installed configuration.
Model number and installed configuration are found
on the burner and in the Installation, Operation and
Service Manual. See Page 5, Figure 3 through Page
7, Figure 11

. Write the proper clearance dimensions

in permanent ink according to your model number
and configuration in the open spaces on the tag.

2.2 Corrosive Chemicals

Roberts-Gordon LLC cannot be responsible for
ensuring that all appropriate safety measures are
undertaken prior to installation; this is entirely the
responsibility of the installer. It is essential that the
contractor, the sub-contractor, or the owner identifies
the presence of combustible materials, corrosive
chemicals or halogenated hydrocarbons* anywhere
in the premises.

* Halogenated Hydrocarbons are a family of
chemical compounds characterized by the
presence of halogen elements (fluorine, chlorine,
bromine, etc.). These compounds are
frequently used in refrigerants, cleaning agents,
solvents, etc. If these compounds enter the air
supply of the burner, the life span of the heater
components will be greatly reduced. An outside air
supply must be provided to the burners whenever
the presence of these compounds is suspected.
Warranty will be invalid if the heater is exposed to
halogenated hydrocarbons.

2.3 National Standards and Applicable Codes

All appliances must be installed in accordance with
the latest revision of the applicable standards and
national codes. This refers also to the electric, gas
and venting installation. Note: Additional standards
for installations in public garages, aircraft hangars,
etc. may be applicable.

CAUTION

Product Damage Hazard

Do not use heater in area containing
corrosive chemicals.

Refer to appropriate Material Safety Data
Sheets (MSDS).

Failure to follow these instructions can result
in product damage.

Advertising
This manual is related to the following products: