Serial communications, 1 rs-232 connection and port configuration, 2 serial command syntax – Runco PL-61DHD User Manual

Page 57: Table 6-1 . serial commands, Rs-232 connection and port configuration, Serial command syntax, Serial communications on, Pre l iminar y

Advertising
background image

Runco PlasmaWall Owner’s Operating Manual

47

PRE

L

IMINAR

Y

6.1
RS-232 Connection
and Port Configuration

To interface the PlasmaWall with a home theater automation/control system or a PC
running terminal emulation software, connect it to the RS-232 output of the DHD
Controller as shown in Figure 3-4. Connect your control system or PC to the RS-232 input
of the DHD Controller as shown in Figure 3-9.

Configure the RS-232 controller or PC serial port as follows: no parity, 8 data bits, 1 stop
bit and no flow control. Set the baud rate to 19200, to match that of the DHD Controller
RS-232 port.

6.2
Serial Command
Syntax

Serial commands to the DHD Controller take the following form:

• Commands are not case-sensitive.

• For a single command that takes no parameters, type the command followed by a

carriage return; for example, to set the aspect ratio to Letterbox, type

LETTERBOX <Return>

.

• For a single command that takes a parameter, type the command, a space or a

comma and the desired value followed by a carriage return; for example, to set the
brightness to -10, type

BRIGHTNESS -10 <Return>

or

BRIGHTNESS,-10 <Return>

.

• You can also send a string of multiple commands on a single line, separated by

commas. For example,

COMPOSITE,BRIGHTNESS 100,ANAMORPHIC <Return>

switches to the Composite video input, sets the brightness to 100 and sets the aspect
ratio to Anamorphic. Command strings can be up to 255 characters long.

Table 6-1 lists the RS-232 command set. The “Parameter (min/max)” column shows the
valid parameter ranges, or “NA” for commands that take no parameters.

When you enter a valid command, the DHD Controller executes it and acknowledges it
with a plus sign on the command line (+ >). When you enter an invalid command -- one
that is misspelled or followed by values outside the valid range for that command -- the
DHD Controller ignores it and returns a minus sign (- >).

6. Serial Communications

Table 6-1. Serial Commands

Command

Parameter

(min/max)

Value

Stored?

Description

POWER

0/1

NA

Turns display on and off

ON

NA

NA

Turns display on

OFF

NA

NA

Turns display off

COMPOSITE

NA

YES

Selects the Composite video input

SVIDEO1

NA

YES

Selects the S-Video 1 input

SVIDEO2

NA

YES

Selects the S-Video 2 input

COMPONENT

NA

YES

Selects the Component input