Controller identification register, Current amps limit registers – RoboteQ Dual Channel Digital Motor Controller AX2550 User Manual

Page 144

Advertising
background image

Serial (RS-232) Controls and Operation

144

AX1500 Motor Controller User’s Manual

Version 1.9b. June 1, 2007

Controller Identification Register

Address:

^8A

Access:

Read Only

Effective:

Instantly

This register may be used to query the Controller’s model and some of its optional hard-
ware configurations.

Current Amps Limit Registers

Address:

^8B - Channel 1
^8C - Channel 2

Access:

Read Only

Effective:

Instantly

These registers can be polled to view what the Amps limit is at the current time. This limit
normally is the one that is preset by the user except when the controller is operating at
high temperature, in which case the allowable current drops as temperature rises. See
“Temperature-Based Current Limitation” on page 42.

To convert the register value in Amps, divide the reading by 4.

5

Confirmed Short Circuit

Permanent

6

Confirmed Encoder Error

Permanent

7

Emergency Stop Pressed

Permanent

TABLE 26. Controller Identification Register Definition

Bit

Model or Function

0

AX500

1

AX1500

2

AX2500

3

AX3500

4

Unused

5

Encoder Present

6

Short Circuit Detection Present

7

Unused

TABLE 25. Controller Status Register Definition

Bit

Fault Condition

Effect