Combustibles, Warning – Roberts Gorden UHA SERIES 200 User Manual

Page 10

Advertising
background image

WARNING

Fire Hazard

Some objects will catch fire or explode when placed

close to heater.
Keep all flammable objects, liquids and vapors the

required clearances to combustibles away from heater.
Failure to follow these instructions can result in death,

injury or property damage.

COMBAT

®

UHA U

NIT

H

EATER

I

NSTALLATION

O

PERATION

AND

S

ERVICE

M

ANUAL

4

Figure 1: Installation Clearances and Clearances to Combustibles

6"**

(15 cm)

31"

(79 cm)

3"

6"

(15 cm)

Clearances to Combustibles

24" for

adequate

air flow access

axial fan.

10'

(3 m)

Wall

Terminal

Roof Terminal

Top

20' (6.0 m) - 30' (9.1 m)

Max. Mounting Height*

Installation Clearances

(Optional separated

combustion concentric

venting shown.)

* Recommended mounting height varies with heater input.
Heaters may be mounted at a higher level if destratification
fans are installed.
Note: Venting directly from top of heater not applicable
on Models 150 - 400.

Clearance to Vent: 2" (5 cm)

**31" (79 cm) minimum is necessary
for servicing.

The heater must always be installed at least 6' (2 m) above the floor.
The vent pipe must have clearance from combustibles by 2" (5 cm).
If installed at low levels where individuals can come in contact with hot heat
exchanger components, adequate guarding must be provided.