13.2 Troubleshooting For Automatic Ignition Burner Systems

If problems persist, contact

Roberts-Gordon, LLC at

www.rg-inc.com

Heater Operating

TROUBLESHOOT ENDS. No

Trace fault in supervision

system. See

Troubleshooting

for Flame Supervision

System section.

Yes

Is ignition control showing

a "2 flashes" led code?

No

Is the flame current at

least 1 µAmp DC when

the flame ignites?

Ignition control faulty;

replace.

See Ignition Control section.

Is ignition lead okay and

connected?

Is spark electrode okay?

Yes

Replace valve.

Is the gas valve operating?

To test valve, See

Troubleshooting for Gas

Valves section.

No

Does the flame light?

No

Yes

Wait 30 - 40 seconds.

Does ignition spark operate? No

Yes

Flue fan faulty; replace

Burner control faulty or wiring

connections faulty. Repair

or replace as necessary

Check for too much vent/air inlet duct. Check for blockage in

vent and combustion air circuit. Check for faulty air pressure

switch. Check pressure switch hoses for leaks or cracks.

Do not attempt to circumvent pressure switch circuit to

place unit in operation.See Pressure Switch section for details.

Does air pressure switch

change over?

No

Yes

Turn on controls.

Is 120 V supply at fan

connections?

Does flue fan run?

No

Are external controls

(i.e. Thermostat) on?

No

Yes

Yes

Is ignition control showing

a "4 flashes" led code?

No

Yes

Press in reset button on

manual reset limit switch

Turn on supplies.

Are gas & electrical

supplies on?

Yes

Start

No

Yes

No

Yes

WARNING

Electrical Shock Hazard

Do not touch ignition components.

Voltage from ignition components is high.

Failure to follow these instructions can

result in death or electrical shock.

For your safety and optimum heater performance,
use only ROBERTS GORDON

®

replacement parts.

Conduct start-up procedure as shown

on Page