4 combustion fan vertical installation – Roberts Gorden UHA SERIES 200 User Manual

Page 40

Advertising
background image

COMBAT

®

UHA U

NIT

H

EATER

I

NSTALLATION

O

PERATION

AND

S

ERVICE

M

ANUAL

34

14.4 Combustion Fan Vertical Installation

Vent Box

Outlet

Gasket

Flue Fan

Vent Box

Screws

Flue

Adapter

Flue Adapter

to Flue Fan

screws

Rear Panel

Hole

Disconnect

electrical connections

at plug in tabs.

Mounting Plate

to Vent Box

Screws

Mounting

Plate

Gasket

Air Plate

Mounting Plate

to Flue Fan

Screws

Vent Box

Gasket

Remove screws securing outlet
flange to the flue adapter.

Refit in reverse order.

Remove screws securing flue
fan mounting plate to vent box.
Remove screws securing
mounting plate to fan.
Refit in reverse.
Use new gaskets.
Ensure sealed joints.
Ensure mounting plate orifice is
clear and not obstructed.

MODEL

UHA[S]

150 - 175

UHA[S]

200 - 300

UHA[S]

350 - 400

Exhaust Fan P/N

90710405

90710403

90710402

IT IS IMPORTANT THAT ONLY THE CORRECT COMBUSTION FAN SPECIFIED FOR EACH MODEL
TYPE IS USED WHEN REPLACING THESE ITEMS.

Carry out a start-up after working on or changing a combustion fan. See Page 22, Section 11.

Advertising