SECTION 6: V

ENTING

9

6.7 Vent Material

Vent material may be single wall 26 ga. (minimum)
galvanized steel or equal thickness stainless steel.
Completely seal all joints, refer to Page 7, Section
6.2
.

If penetrating a combustible wall or roof, a listed
thimble with 2" (5 cm) clearance must be used.
Where local codes permit, a single section of type
B-1 vent material may be used at the roof or wall
penetration instead of a thimble. Ensure vent
manufacturer's clearance from vent material is
maintained. Seal annular space of the type B-1 vent
as well as all joints in the remaining vent.

Figure 3: Vent and Roof Detail

Roof

Vent

Terminal

Listed Thimble

Flashing

or Rain Collar

Vent

2" Air Gap to

Combustible Material

Figure 4: Standard Vented Heater - Vertical and Horizontal Vent Termination

Vent

Terminal

4" Dia.Vent

Flashing

(By Others)

Listed

Thimble

(2" Clearance)

Vent Terminal

Vertical

Option

Horizontal

Option

Vent

Listed

Thimble

(2" Clearance)

Flashing

(By Others)

12" (31 cm)

Minimum

Condensate

Trap to Drain

(Optional)

Note: Vent supports

not shown.

90°

Bend

Model

Vent Diameter

Part Number

UHA 150 - 400

4" (10 cm)

90502102