SECTION 13: T

ROUBLESHOOTING

27

SECTION 13: TROUBLESHOOTING

13.1 General

Ensure proper air flow

clearance for axial fan.

Open louvers slightly.

Replace axial fan if it does

not operate.

If problems persist, contact

Roberts-Gordon, LLC at

www.rg-inc.com

Heater Operating

TROUBLESHOOT ENDS. No

Replace limit switch.

The limit switch has

tripped. See Manual Reset

Limit Switch Figure.

No

Use Troubleshooting for

Automatic Ignition Burner

Systems section to test burner.

Has burner “Locked Out”?

Yes

No

With external controls (i.e.

thermostat) on, does the

burner continue through the

heating cycle?

No

Yes

Does the combustion

fan run?

No

Use Troubleshooting for

Combustion Fan section to

test fan.

Yes

Yes

Burner has locked out due

to ignition failure. Use

Troubleshooting for Automatic

Ignition Burner Systems

section to test burner.

Is ignition control showing a

"2 flashes" led code?

Yes

No

Yes

Fan and limit switch are

operating normally.

Replace temperature

limit switch.

Wait 10-15 minutes for limit

switch to cool. Does fan

stop running?

No

Yes

Does axial fan run

immediately upon supplying

power to heater?

Yes

No

Turn on supplies.

Are gas & electrical

supplies on?

No

Yes

Start

WARNING

Explosion Hazard

Installation must be done by a registered installer/

contractor qualified in the installation and service of

gas-fired heating equipment or your gas supplier.

Failure to follow these instructions can result in death,

injury or property damage.