SECTION 14: R

EPLACEMENT

P

ARTS

35

14.5 Pressure Switch

Pull off 3 way connector. Spring open plastic clips of
mounting cradle. Replace with correct type of
pressure switch for model. The pressure switches
are color coded for each pressure setting.

Carbon Monoxide Hazard

Use correct pressure switch specified for each model.

Use of incorrect pressure switch or disabling

pressure switch circuit could cause unsafe condition.

Failure to follow these instructions can result in

death or serious injury.

WARNING

Carry out a commission after working on or
changing a pressure switch. See Page 19, Section
10
.

Pressure Switch

UHA[S]

150 - 175

UHA[S]

200 - 225

UHA[S]

250

UHA[S]

300 - 350

UHA[S]

400

P/N

90439802

90439808

90439803

90439807

90439808

Color Code

yellow

orange

gray

brown

orange

Set Point in. w.c.

.32

.79

.41

.68

.79