13.4 Troubleshooting for Gas Valves

Valve faulty.

Replace with one of

correct type.

Fault elsewhere.

Correct pressure problem.

If problems persist, contact

Roberts-Gordon, LLC at

www.rg-inc.com

Valve Operating

TROUBLESHOOT ENDS.

No

Yes

Valve or ignition control

faulty. Replace with

one of correct type.

Does gas pressure at

outlet of valve return to zero or

lower when valve turns off?

No

Yes

Does gas pressure at outlet

of the valve rise when

valve turns on?

No

Yes

Is gas pressure at inlet of the

valve correct for gas type?

Note pressure found.

No

Yes

START

13.5 Troubleshooting for Combustion Fan

If problems persist, contact

Roberts-Gordon, LLC at

www.rg-inc.com

Fan Operating

TROUBLESHOOT ENDS. No

Fan motor faulty.

Replace with correct type.

Check fan motor leads for

loose connections.

Correct power

supply problem.

Yes

START

Does fan turn on and

off while burner is firing

continously?

No

Yes

Does combustion fan run

automatically when there

is a call for heat?

No

Yes

For your safety and optimum heater performance,
use only genuine ROBERTS GORDON

®

replacement parts.

Conduct start-up procedure as shown

on Page 19, Section 10.