Figure 10: Automatic Burner Control Sequence

Burner Sequence for Ignition Control

Flame Signal

Start Gas Valve

Ignition Spark

Thermostat 24 V

SHUT DOWN

RUN

START

ts = 10 seconds

Signals Output By Control

Required Incoming Signals

Flue Fan

Pressure

Switch

P

C

NO

NC

30 Sec. Purge*

*Purge time begins at pressure switch change over.

Axial Fan

30 Sec. Delay

90 Sec. Delay

30 Sec. Post Purge

If at any stage the flame fails, the control will retry
for ignition. The control has four trials for ignition
before a one hour lockout.

Figure 11: Gas Valve for Models UHA(S) 150 - 400

Description

Part Number

Gas Valve 150 - 225 NG

90032505

Gas Valve 150 - 225 LP

90032506

Gas Valve 250 - 400 NG

90032520

Gas Valve 250 - 400 LP

90032521

½PSI

IN

C

ON

OFF

Regulator

Outlet
Pressure

Gas Inlet

Inlet Pressure

Top View

End View