3 ignition electrode and flame probe – Roberts Gorden UHA SERIES 200 User Manual

Page 39

Advertising
background image

SECTION 14: R

EPLACEMENT

P

ARTS

33

14.3 Ignition Electrode and Flame Probe

Flame

Probe

Ignition

Electrode

Remove

Screw

Ignition

Electrode

Burners

Flame

Probe

Burners

Burner Compartment

Front Views

Remove all

burner compartment

screws to remove

the burner

compartment and

access the

"Front View".

Limit

Thermostat

.120

(3 mm)

spark

gap

Description

Part Number

Qty.

Spark Electrode

90427411

1

Automatic Ignition Flame Probe

90439300

1

Inshot Burners (150, 175)

92000001

1

Inshot Burners (200 - 400)

92000002

1

Limit Switch (150 - 400)

90412103

1

Limit Switch (300 - 400)

90412105

2

To replace the electrode or flame probe, remove the electrical lead and screw.
Pull out from mounting. Refit in reverse ensuring that the gap to burner is as shown in the
front view of the burner compartment.