Installing the water heater.

A new combination temperature and pressure relief valve, complying with the Standard for Relief Valves

and Automatic Gas Shut-Off Devices for Hot Water Supply Systems, ANSI Z21.22, is supplied and must

remain in the opening provided and marked for the purpose on the water heater. No valve of any type

should be installed between the relief valve and the tank. Local codes shall govern the installation of

relief valves.

Relief Valve

The pressure rating of the relief valve

must not exceed 150 PSI, the maximum

working pressure of the water heater as

marked on the rating plate.
The Btuh rating of the relief valve must

equal or exceed the Btuh input of the

water heater as marked on its rating plate.
Position the outlet of the relief valve

above a suitable open drain to eliminate

potential water damage. Piping used

should be of a type approved for hot water

distribution.

The discharge line must be no smaller

than the outlet of the valve and must

pitch downward from the valve to allow

complete drainage (by gravity) of the

relief valve and discharge line.
The end of the discharge line should not

be threaded or concealed and should be

protected from freezing. No valve of

any type, restriction, or reducer coupling

should be installed in the discharge line.

To Fill the Water Heater

Make certain that the drain valve is

closed, then open the shut-off valve in the

cold water supply line.
Open each hot water faucet slowly to

allow the air to vent from the water

heater and piping.
A steady flow of water from the hot water

faucet(s) indicates a full water heater.

Do not allow the flammable vapor sensor

to become submerged in water.

WARNING: The tank

must be full of water before

heater is turned on. The

water heater warranty does

not cover damage or failure

resulting from operation

with an empty or partially

empty tank.

Condensation

Condensation can form on the tank

when it is first filled with water.

Condensation might also occur with a

heavy water draw and very cold inlet

water temperatures.
Drops of water falling on the burner can

produce a sizzling or pinging sound.
This condition is not unusual, and will

disappear after the water becomes heated.

If, however, the condensation continues,

examine the piping and fittings for

possible leaks.

NOTICE: Additional information on this

subject may be found at www.rheem.com,

under Rheem Water Heating, "Support",

scroll down to the Technical Service

Section and to Bulletins 1400 Series

Section and choose Bulletin #1402..