Gas Valve LED Codes

32

CAUTION: Make certain power to water heater is “OFF” before removing protective cover FOR ANY REASON.

CAUTION: Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and

dangerous operation. VERIFY PROPER OPERATION AFTER SERVICING.

CAUTION: For your safety DO NOT attempt repair of gas piping, remote control, burners, vent connectors or other

safety devices. Refer repairs to qualified service personnel.

LED Status

Problem

Solution

○ ○

▼ A B C

● ○ ○ ● ○ ○

An open earth ground circuit to the

ignition system.

1. Check that the earth ground connection is properly

connected.

2. Check that the ground conductor on the water

heater is properly connected.

○ ○

▼ A B C

● ○ ● ○ ● ○

Wiring error or a high resistance to

earth ground.

1. Check proper connection of line

neutral and hot wires.

2. Check that the water heater is securely connected

to earth ground.

○ ○

▼ A B C

● ○ ● ○ ○ ○

Pressure switch remained closed

longer

than 5 seconds after the call for

heat began.

1. Pressure switch wiring is incorrect.

2. Replace pressure switch.

○ ○

▼ A B C

● ○ ● ○ ○ ●

Pressure switch remained open lon-

ger

than 5 seconds after the combustion

blower was energized.

1. Pressure switch wiring is incorrect.

2. Pressure switch tubing is not connected correctly.

3. Air intake or exhaust obstructed.

○ ○

▼ A B C

● ○ ● ○ ● ●

Error in the hot surface ignitor cir-

cuit.

1. Check that all wiring is correct and secure.

2. Replace hot surface ignitor.

○ ○

▼ A B C

● ○ ○ ● ● ○

System in lockout.

1. Gas supply is off or too low to operate.

2. Hot surface ignitor not positioned

correctly.

3. Low voltage to the water heater.

4. Electric polarity to unit is incorrect - test and cor-

rect.

5. Combustion shut-off device tripped, contact ser-

vice agency.

○ ○

▼ A B C

● ○ ○ ○ ● ●

Problem in the gas valve driver cir-

cuit.

1. Turn power to the water heater off for 10 seconds

and then back on.

2. Replace gas control valve.

○ ○

▼ A B C

● ○ ● ● ● ○

Problem with the internal circuit.

1. Turn power to the water heater off for 10 seconds

and then back on.

2. Replace gas control valve.

○ ○

▼ A B C

● ● ● ● ● ●

Problem with the internal circuit.

1. Turn power to the water heater off for 10 seconds

and then back on.

2. Replace gas control valve.

○ ○

▼ A B C

● ○ ○ ○ ● ○

Flame signal sensed out of

proper sequence.

1. Replace gas control valve.

○ ○

▼ A B C

● ○ ○ ● ● ●

ECO activated.

1. Replace gas control valve.

○ ○

▼ A B C

● ○ ● ● ○ ○

One of the temperature adjust

buttons stuck closed.

1. Press and release each of the buttons once.

2. Replace gas control valve.

○ ○

▼ A B C

● ○ ● ● ○ ●

Water temperature sensor is either open

or short circuited.

1. Check that all wiring is correct and secure.

2. Replace gas control valve.

○ ○

▼ A B C

● ○ ○ ● ○ ●

Unit shuts down.

1. Check for correct wiring to FV sensor.

2. Check for open circuits to FV sensor.

3. Replace FV sensor.

○ ○

▼ A B C

● ○ ○ ○ ○ ●

Unit shuts down and in lockout.

1. FV sensor detected presence of flammable vapors.

2. Contact a service agency.