Before you call for service – Ruud PowerVent AP14236 User Manual

Page 31

Advertising
background image

31

Problem

Possible Causes

What To Do

Rumbling noise

Scale and sediment

Drain the water heater to remove scale and sediment from

the tank. Refer to the top of page 26.

Relief valve

Pressure build up

This is an unacceptable condition and must be

producing popping

caused by thermal

corrected. Contact the water supplier or plumbing

noise or draining

expansion to a

contractor on how to correct this. Do not plug the

closed system.

relief valve outlet.

Not enough or

Water usage may have

Wait for the water heater to recover after an

no hot water

exceeded the capacity

abnormal demand.

of the water heater.

Low gas pressure.

Check gas supply pressure and manifold pressure.

The gas control (thermostat)

See the “Water Temperature Setting” of The Water

may be set too low.

Heater section of this manual.

Leaking or open hot

Make sure all faucets are closed.

water faucets.

Check valve error codes.

Refer to gas valve error code table on page 30.

“ON/OFF” switch turned off.

Turn “ON”.

Blower unplugged.

Plug in. Verify power supply (120VAC).

Combustion Shutoff System

Contact a qualified service technician.

tripped

Water is too hot

The gas control (thermostat)

See the “Water Temperature Setting” of The Water

is set too high.

Heater section of this manual.

Gas Control (Thermostat)

Contact a qualified service technician to replace the

Defective.

gas control (thermostat).

Before You Call For Service…

Troubleshooting Tips
Save time and money! Review the charts on the following pages first and you may not need to call for service.

This water heater incorporates a combustion shut off device that shuts the operation of the water heater down

if undesirable combustion conditions occur, such as the presence of flammable vapors or blockage of the

combustion air inlet openings. Please contact a qualified Service Technician if this occurs.

CAUTION: For your safety DO NOT attempt repair of gas piping, gas control (thermostat), burners, vent connectors or

other safety devices. Refer repairs to qualified service personnel.

CAUTION: Make certain power to water heater is “OFF” before removing protective cover FOR ANY REASON.

CAUTION: Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and

dangerous operation. VERIFY PROPER OPERATION AFTER SERVICING.

Advertising