Installing the water heater, Combustion and ventilation air, Corrosive atmospheres – Ruud PowerVent AP14236 User Manual

Page 8: Inspect shipment

Advertising
background image

8

Installing the water heater.

Combustion and Ventilation Air

Ventilation (ambient) air temperature

must be 100°F or less. Proper operation

of the water heater requires air for

combustion and ventilation. Provisions

for combustion and ventilation air

must comply with referenced codes and

standards.
DO NOT block or obstruct any of the

combustion air inlet openings located

around the perimeter of the water

heater. A minimum of 1” is required

between these combustion air inlet

openings and any obstruction.
NOTICE: If the water heater is

installed in an unconfined space within a

building of conventional frame, masonry

or metal construction, infiltration

air is normally adequate for proper

combustion and ventilation. If the

water heater is installed in a confined

space, provisions for combustion and

ventilation air must be made.
DO NOT obstruct or block the

Flammable Vapor Sensor.
A confined space is one having a volume

of less than 50 cubic feet per 1000 Btuh

of the aggregate input of all appliances

within that space.
The air must be supplied through two

permanent openings of equal area. One

is to be located within 12” above the floor

and the other is to be located within 12”

from the ceiling.

The minimum net free area of each opening

must not be less than one square inch

per 1000 Btuh of the total input rating

of all the appliances in the enclosure

(but not less than 100 square inches), if

each opening communicates with other

unconfined areas inside the building.
Buildings of unusually tight construction

shall have the combustion and ventilation

air supplied from outdoors, or a freely

ventilated attic or crawl space.
If air is supplied from outdoors, directly or

through vertical ducts, there must be two

openings located as specified above and

each must have a minimum net free area

of not less than one square inch per 4000

Btuh of the total input rating of all the

appliances in the enclosure.
If horizontal ducts are used to

communicate with the outdoors, each

opening must have a minimum net free

area of not less than one square inch per

2000 Btuh of the total input rating of all

the appliances in the enclosure. If ducts

are used, the minimum dimensions of

rectangular air ducts shall not be less than

3”.
NOTICE: If the duct openings which

supply combustion and ventilation air

are to be covered with a protective

screen or grill, the net free area

(openings in the material) of the

covering material must be used in

determining the size of the openings.

Protective screening for the openings

MUST NOT be smaller than 1/4”mesh

to prevent clogging by lint or other

debris.

Corrosive Atmospheres

The air in beauty shops, dry cleaning

establishments, photo processing

labs, and storage areas for liquid and

powdered bleaches or swimming pool

chemicals often contain such halogenated

hydrocarbons.
An air supply containing halogenated

hydrocarbons may be safe to breathe,

but when it passes through a gas flame

corrosive elements are released that

will shorten the life of any gas burning

appliance.
Propellants from common spray cans

or gas leaks from A/C and refrigeration

equipment are highly corrosive after

passing through a flame.
The water heater warranty is voided when

failure of the heater is due to operation in

a corrosive atmosphere.

NOTICE: The water heater

should not be installed near

an air supply containing

halogenated hydrocarbons.

Inspect Shipment

Inspect the water heater for possible damage. Check the markings on the rating plate of

the water heater to be certain the type of gas supplied corresponds to the water heater

requirements.

NOTICE: Do not install the

water heater in attics where

the temperature may exceed

100°F. This water heater is

equipped with a temperature

sensing device that will

shut off the water heater

if the maximum allowable

vent pipe temperature is

exceeded.